RMC100 and RMCWin User Manual
4-42
It is already set to 21 ms, which is correct. If the MDT transducer is a clevis-mount type, choose
5 ms.
Click Update RMC.
Double-click the Axis 0 Config Word, which opens the following window:
In the Transducer Type field, select Start/Stop (Rising Edge).
In the Pressure Axis field, select Aux 2 as the pressure axis. This assigns the pressure axis to
this position axis. This is necessary for the RMC to be able to control position and pressure on
axis 0.
Leave all the other settings as they are.
Click OK.
Issue a Set Parameters (P) command to Axis 0.
6. Scaling the pressure/force axis.
To configure the pressure axis, the following steps are performed:
Click on any Aux 2 field.
On the Tools menu, click Scale/Offset Calibration. The following window opens: