3. Instruction Set
3-445
reset after CH0 (Y0, Y1) pulse output is completed.
M1524 Auto-reset CH1 (Y2, Y3) when high speed pulse output completed. M524 will be
reset after CH1 (Y2, Y3) pulse output is completed.
M1534 Enable ramp-down time setting on Y0. Has to be used with D1348
M1535 Enable ramp-down time setting on Y2. Has to be used with D1349
2. Special registers:
D1026: Pulse number for masking Y0 when M1156 = ON (Low word). The function is
disabled when set value0. (Default = 0 )
D1027: Pulse number for masking Y0 when M1156 = ON (High word). The function is
disabled when set value0. (Default = 0 )
D1135: Pulse number for masking Y2 when M1156 = ON (Low word). The function is
disabled when set value0. (Default = 0 )
D1136: Pulse number for masking Y2 when M1156 = ON (High word). The function is
disabled when set value0. (Default = 0 )
D1030: Low word of the present value of CH0 (Y0, Y1) pulse output
D1031: High word of the present value of CH0 (Y0, Y1) pulse output
D1131: Input/output percentage value of CH0 (Y0, Y1) close loop control. Default: K100
D1132: Input/output percentage value of CH1 (Y2, Y3) close loop control. Default: K100
D1244:
Idle time (pulse number) setting of CH0 (Y0, Y1) The function is disabled if set
value0.
D1245:
Idle time (pulse number) setting of CH2 (Y2, Y3) The function is disabled if set
value0.
D1336: Low word of the present value of CH1 (Y2, Y3) pulse output
D1337: High word of the present value of CH1 (Y2, Y3) pulse output
D1340: Start/end frequency of the 1st group pulse output CH0 (Y0, Y1). Default: K100
D1352: Start/end frequency of the 2st group pulse output CH1 (Y2, Y3). Default: K100
D1343:
Ramp up/down time of the 1st group pulse output CH0 (Y0, Y1). Default: K100
D1353:
Ramp up/down time of the 2nd group pulse output CH1 (Y2, Y3). Default: K100
D1348: CH0(Y0, Y1) pulse output. When M1534 = ON, D1348 stores the ramp-down
time. Default: K100
D1349: CH1(Y2, Y3) pulse output. When M1535 = ON, D1349 stores the ramp-down
time. Default: K100