Error
code
Description Remedy
16#0034
The setting of the station address
of COM1 is incorrect. (SM9)
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
16#0035
The setting of the communication
type of COM1 is incorrect. (SM9)
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
16#0036
The interval of retrying the
sending of the command through
COM1 is set incorrectly.(SM9)
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
16#0037
The number of times the sending
of the command through COM1
is retried is set incorrectly. (SM9)
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
16#0038
The communication setting of
COM2 is incorrect. (SM9)
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
16#0039
The setting of the station address
of COM2 is incorrect. (SM9)
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
16#003A
The setting of the communication
type of COM2 is incorrect. (SM9)
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
16#003B
The interval of retrying the
sending of the command through
COM2 is set incorrectly.(SM9)
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
16#003C
The number of times the sending
of the command through COM2
is retried is set incorrectly. (SM9)
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
16#005D
The CPU module does not detect
a memory card. (SM453)
Check whether a memory card is inserted into the CPU
module correctly.
16#005E
The memory card is initialized
incorrectly. (SM453)
Check whether the memory card breaks down.
16#005F
The data is read from the
inexistent file in the memory card,
or the data is written into the
inexistent file in the memory card.
(SM453)
Check whether the file path is correct.
16#0060
The default folder can not be
created in the CPU module.
(SM453)
Check whether the capacity of the memory card is large
enough, or whether the memory card breaks down.
16#0061
The capacity of the memory card
is not large enough. (SM453)
Check whether the capacity of the memory card is large
enough.
16#0062
The memory card is write
protected. (SM453)
Check whether the memory card is write protected.