Chapter 9 Troubleshooting
9-23
Error
code
Description Remedy
16#A404
The signal received by channel 4
exceeds the range of inputs
which can be received by the
hardware. (The ERROR LED
indicator is ON.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 4 exceeds
the range of inputs which can be received by the
hardware.
16#A405
The signal received by channel 5
exceeds the range of inputs
which can be received by the
hardware. (The ERROR LED
indicator is ON.)
Check the module parameter in HWCONFIG.
Check whether The signal received by channel 5
exceeds the range of inputs which can be received by the
hardware.
16#A406
The signal received by channel 6
exceeds the range of inputs
which can be received by the
hardware. (The ERROR LED
indicator is ON.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 6 exceeds
the range of inputs which can be received by the
hardware.
16#A407
The signal received by channel 7
exceeds the range of inputs
which can be received by the
hardware. (The ERROR LED
indicator is ON.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 7 exceeds
the range of inputs which can be received by the
hardware.
16#A600 Hardware failure
1. Check whether the backplane is normal.
2. Check whether the module operate normally.
16#A601 The external voltage is abnormal.
Check whether the external 24 V power supply to the
module is normal.
16#A602
Internal error
The CJC is abnormal.
Please contact the factory.
16#A603
Internal error
The factory correction is
abnormal.
Please contact the factory.
16#A800
The signal received by channel 0
exceeds the range of inputs
which can be received by the
hardware. (The ERROR LED
indicator is OFF.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 0 exceeds
the range of inputs which can be received by the
hardware.
16#A801
The signal received by channel 1
exceeds the range of inputs
which can be received by the
hardware. (The ERROR LED
indicator is OFF.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 1 exceeds
the range of inputs which can be received by the
hardware.
16#A802
The signal received by channel 2
exceeds the range of inputs
which can be received by the
hardware. (The ERROR LED
indicator is OFF.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 2 exceeds
the range of inputs which can be received by the
hardware.
16#A803
The signal received by channel 3
exceeds the range of inputs
which can be received by the
hardware. (The ERROR LED
indicator is OFF.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 3 exceeds
the range of inputs which can be received by the
hardware.
16#A804
The signal received by channel 4
exceeds the range of inputs
which can be received by the
hardware. (The ERROR LED
indicator is OFF.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 4 exceeds
the range of inputs which can be received by the
hardware.