CHAPTER 2: INSTALLATION STARTER TYPES
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–21
2.3 Starter types
2.3.1 Full-voltage non-reversing starter
Figure 25: Full-voltage non-reversing starter wiring
The full-voltage non-reversing starter type is a full voltage or across-the-line non-reversing
starter.
When a start control is received, the pre-contactor relay (if any) is picked up for the set pre-
contactor time. When the pre-contactor timer times out, relay1 picks up and seals-in,
picking up contactor M, which starts the motor. When a stop control is received, relay1
drops out, contactor M drops out, and the motor stops. The pre-contactor is omitted on
forced starts (for example, UVR Immediate, External Start).
NOTE
NOTE:
Connect AUX VT to the Control Supply for correct operation of the UV Restart feature and
readings of inputs
A
B
C
M M M
MOTOR
M
Stator Thermistor
M
Field Stop
Field Start
Reset
Core Balance CT
Contactor
MM300
Low Voltage
Motor
Manager
D2
D1
D8
D7
D6
D5
D4
D3
CT Module
PSU
C1
C2
C3
C4
C5
C6
C7
C8
I/O Module- Type C
C9
C10
C11
C12
C13
C14
I
C
I
B
I
A
Aux VT
+
-
Com
+
CPU
-
R
I
Surge Grd
Core
Balance
Thermistor
RS485
CT2
CT3
G/F
CT1
RS485 Serial Link
Ground at one point
N
L
IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 Com
Relay 1Relay 2
LN
Order Code : MM300-XEHSSCA