Delta PG-40 Specifiche Pagina 88

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 179
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 87
5
VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-53
08 - 21
Auto Reset Time at Restart after Fault
Factory Setting: 600
Settings 00 to 60000 sec Unit: 1
This parameter should be used with Pr.08-14. For example: Pr.08-14 is set to 10 and
Pr.08-21 is set to 600s (10 min), if there is no fault over 600 seconds from the restart for
the previous fault, the auto reset times for restart after fault will be reset to 10.
08 - 22
Compensation Coefficient for Motor Instability
a
Factory Setting: 00
Settings 00~1000 Unit: 1
This parameter can improve the motor instability situation.
Vedere la pagina 87
1 2 ... 83 84 85 86 87 88 89 90 91 92 93 ... 178 179

Commenti su questo manuale

Nessun commento